2 core Aluminium / Copper


2 core Aluminium / Copper

SIZE NOMINAL INSULATION THICKNESS MINIMUM INNER SHEATH THICKNESS MINIMUM OUTER SHEATH THICKNESS APPROX. OVERALL DIA OF CABLE ±2MM APPROX. WEIGHT OF CABLE MAX. CONDUCTOR DC RESISTANCE at 20 ° C NOMINAL CURRENT RATING ALUMINIUM CONOUCTOR NOMINAL CURRENT RATING COPPER CONDUCTOR
A2XY 2XY ALUMINIUM COPPER GROUND AIR GROUND AIR
mm2 mm mm mm mm Kg/Km Ohm/Km AMPS
2C X 4 0.70 0.30 1.80 12.00 180 240 7.410 4.61 36 32 45 40
2C X 6 0.70 0.30 1.80 13.00 220 300 4.610 3.08 45 42 57 52
2C X 10 0.70 0.30 1 .80 15 .00 280 400 3.080 1 .83 60 56 75 69
2C X 16 0.70 0.30 1.80 14.00 290 430 1.910 1.15 80 72 96 87
2C X 25 0.90 0.30 2.00 17.00 380 680 1.200 0.727 96 100 125 130
2C X 35 0.90 0.30 2.00 18.50 430 850 0.868 0.524 118 120 150 160
2C X 50 1.00 0.30 2.00 21.00 600 1150 0.641 0.387 145 146 175 195
2C X 70 1.10 0.30 2.00 23.00 750 1520 0.443 0.268 174 180 215 240
2C X 95 1.10 0.40 2.20 26.00 960 2050 0.320 0.193 210 230 260 300
2C X 120 1.20 0.40 2.20 28.00 1160 2450 0.253 0.153 235 260 290 335
2C X 150 1.40 0.40 2.20 31.00 1380 3050 0.206 0.124 265 305 325 385
2C X 185 1 .60 0.50 2.40 34.50 1720 3750 0.164 0.0991 300 345 365 445
2C X 240 1.70 0.50 2.60 39.00 2160 4900 0.125 0.0754 340 410 416 518
2C X 300 1.80 0.60 2.80 43.00 2660 6100 0.100 0.0601 385 475 470 600
2C X 400 2.00 0.60 3.00 48.00 3300 7850 0.0778 0.0470 450 550 530 680
SIZE NOMINAL INSULATION THICKNESS MINIMUM INNER SHEATH THICKNESS NOMINAL ARMOUR STRIP MINIMUM OUTER SHEATH THICKNESS APPROX. OVERALL DIAOF CABLE ±2MM APPROX. WEIGHT OF CABLE MAX. CONDUCTOR DC RESISTANCE at 20° C NOMINAL CURRENT RATING ALUMINIUM CONDUCTOR NOMINAL CURRENT RATING COPPER CONDUCTOR
A2XFY 2XFY ALUMINIUM COPPER GROUND AIR GROUND AIR
mm2 mm mm mm mm mm Kg/Km Ohm/Km AMPS
2C X 25 0.90 0.30 4X 0.80 1.40 18.00 610 915 1.200 0.727 96 100 125 130
2C X 35 0.90 0.30 4X0.80 1.40 19.50 700 1050 0.868 0.524 118 120 150 160
2C X 50 1.00 0.30 4X 0.80 1.40 21.50 830 1440 0.641 0.387 145 146 175 195
2C X 70 1.10 0.30 4X 0.80 1.56 24.50 1060 1910 0.443 0.268 174 180 215 240
2C X 95 1.10 0.40 4X0.80 1.56 27.00 1310 2480 0.320 0.193 210 230 260 300
2C X 120 1.20 0.40 4X 0.80 1.56 29.50 1510 2950 0.253 0.153 235 260 290 335
2C X 150 1.40 0.40 4X0.80 1.72 32.00 1760 3610 0.206 0.124 265 305 325 385
2C X 185 1 .60 0.50 4X 0.80 1.72 35.00 2210 4400 0.164 0.0991 300 345 365 445
2C X 240 1.70 0.50 4X 0.80 1.88 39.50 2610 5500 0.125 0.0754 340 410 416 518
2C X 300 1.80 0.60 4X0.80 2.04 43.00 3150 6700 0.100 0.0601 385 475 470 600
2C X 400 2.00 0.60 4X 0.80 2.36 49.00 4000 8600 0.0778 0.0470 450 550 530 680
SIZE NOMINAL INSULATION THICKNESS MINIMUM INNER SHEATH THICKNESS NOMINAL ARMOUR WIRE MINIMUM OUTER SHEATH THICKNESS APPROX. OVERALL DIAOF CABLE ±2MM APPROX. WEIGHT OF CABLE

MAX. CONDUCTOR DC RESISTANCE at 20° C NOMINAL CURRENT RATING ALUMINIUM CONDUCTOR

NOMINAL CURRENT RATING COPPER CONDUCTOR
A2XWY 2XWY ALUMINIUM COPPER GROUND AIR GROUND AIR
m m2 mm mm mm mm mm Kg/Km Ohm/Km AMPS
2C X 4 0.70 0.30 1.40 1.24 14.00 400 480 7.410 4.610 36 32 45 40
2C X 6 0.70 0.30 1.40 1.24 15 .00 470 560 4.610 3.080 45 42 57 52
2C X 10 0.70 0.30 1.40 1.24 16.00 570 710 3.080 1.830 60 56 75 69
2C X 16 0.70 0.30 1.40 1.40 16.00 590 780 1.910 1.150 80 72 96 87
  • -THE ABOVE DATA IS APPROXIMATE & SUBJECT TO MANU FACTURING TOLERANCE, 2. DELIVERY LENGTH TOLERANCE +/- 5 %.