FR/FRLS/ZHFR House Wire


FR/FRLS/ZHFR House Wire

APPLICABLE STANDARD : IS 694:2010
CONDUCTOR : THE CONDUCTORS DRAWN FROM 99.97 % BRIGHT ELECTROLYTIC GRADE COPPER WITH MORE THAN 100% CONDUCTIMITYARE. ANNEALED AND BUNCHED TOGETHER.
TYPE INSULATION HRFR PVC COMPOUND : THE BUNCH CONDUCTORS ARE INSULATED wITH SPECIALLY RETARDANT PVC COMPOUND WITH A HIGH INSULATION PROCESS IS CARRIED OUT ON MODERN HIGH SPEED EX ACCURACY AND CONSISTENCY IN PERFORMANCE
FRLS COMPOUND : THE BUNCH CONDUCTORS ARE INSULATED WITH SPECIA SMOKE COMPOUND. DURING A FIRE SITUATION, THE FR-L FLAME. THE SMOKE EMISSION IS ALSO MINIMAL
ZHFR COMPOUND : THE BUNCH CONDUCTORS ARE INSULATED WITH SPECIALLY FORMULATED GRADE OF HALOGEN FREE FLAME RETARDANT (HFFR) COMPOUNDIS USED. THE INSULATION DOES NOT MELT OR DROP IN CASE OF FIRE. THE SMOKE EMITTEDIS TRANSPARENT, NON-TOXICAND MINIMAL
OPERATING TEMPERATURE RANGE : TEMP -15°C TO MAX. +70° C / +85°C
COLOUR : RED, YELLOW, BLUE, BLACK, GREEN, GRAY (AND ALSO OTHER COLOUR REQUEST ON CUSTOMER) COILS 90m,100m, 180m, 27Om BOXES, REELS
PACKING : COILS 90m, 100m, 180m, 270m BOXES, REELS
MARKING : THE CABLES ARE PRINTED WITH GENERIC MARKING JOHNSON HRFR"
APPLICATION : THIS IS A PREMIUM PRODUCT OF ELECTRICAL WIRES FROM " JOHNSON". THESE CABLES ARE IDEALS FOR WIRING IN RESIDENTIAL AND COMMERCIAL COMPLEXES, HIGH-RISE BUILDING, HOTELS, HOSPITALS, SCHOOL, COLLEGES ETC. WHERE DENSITY OF PEOPLE IS HIGH. DURING A FIRE THESE CABLES NOT ONLY EMIT LESS SMOKE AND TOXIC HYDROCHLORIC ACID GAS BUT ALSO RETARD THE SPREADOF FIRE ENABLING THOSE TRAPPED INSIDETO ESCAPESAFELY
FEATURE : - MANUFACTURED FROM BRIGHT ANNEALED 99.97% PURE COPPER CONDUCTORS THESE CABLES HAVE LOW CONDUCTOR RESISTANCE RESULTING IN POWER SAVING.
: - THESE WIRES ARE INSULATED WITH A SPECIAL GRADE PVC COMPOUND FORMULATED AND MANUFACTURED IN-HOUSE.
: - THE INSULATION IS FAR SUPERIOR IN TERMS OF CRITICAL OXYGEN AND TEMPERATURE INDEX. ALSO IN LIGHTTRANSMISSION AND ACID GAS GENERATION.
: - THE SKIN cOLORATION OFFER HIGH INSULATION RESISTANCE AND LONG LIFE.
ISO CERTIFICATION : ISO9001:2015, IS0 45001:2018, IS0 14001 :2015, CE, RoHS
PRODUCT CERTIFICATION : IS 694:2010 7098 P-1 TUV RHEINLAND CERTIFICATE No. R 60160877

NOMINAL CROSS SECTIONAL AREA

NUMBER / NOMINAL DIA OF WIRES* (NOM.) NOMINAL THICKNESS OF INSULATION APPROX OVERALL DIA (+/- 0.2 mm) MAXIMUM DC RESISTANCE OF CONDUCTOR AT 20° C MAX. CURRENT CARRYING CAPACITY AMPS
CASING CONCEALED

0.5

16/0.2 **

0.6

2.10

39.00

4

4

0.75

24/0.2  **

0.6

2.30

26.00

7

6

1

14/0.3 *

0.6

2.70

18.10

12

11

1.5

22/0.3 *

0.7

3.00

12.10

16

13

2.5

36/0.3 *

0.8

3.50

7.41

22

18

4

56/0.3  **

0.8

4.10

4.95

29

24

6

84/0.3 **

0.8

5.10

3.30

37

31

FR FRLS ZHFR
TEST SPECIFICATION SPECIFIEDVALUE TEST SPECIFICATION SPECIFIED VALUE TEST SPECIFICATION SPECIFIED VALUE
CRITICAL OXTYGEN INDEX ASTM-D 2863 29 % MINIMUM CRITCAL OKYGEN INDEX ASTM-D 2863 29 % MINIMUM CRITICAL OXYGEN INDEX ASTM - D 2863 29 % MINIMUM
TEMPERATURE INDEX ASTM - D 2863 250 °C MINIMUM TEMPERATURE INDEX ASTM - D 2863 250 ° C MINIMUM
TEMPERATURE INDEX ASTM - D 2863 250 ° C MINIMUM ACID GAS GENERATION IEC 60754-1 20 % MAXIMUM ACID GAS GENERATION IEC 60754-1 < 0.5%
SMOKE DENSITY RATING ASTM - D 2843 60 % MAXIMUM SMOKE DENSITY RATING ASTM - D 2843 60 % MAXIMUM

CLASS2 STRANDED CONDUCTOR,** CLASSS FLEXIBLE CONDUCTOR
THE NUMBER OF WIRES AND DIAMETER MENTIONED IN THE TABLE ARE APPROXIMATE AND NOMINAL, HOWEVER THEY SHALL MEET THE REQUIREMENTS OF CONDUCTOR RESISTANCE AS PER STANDARDS. IS 8130
THE ABOVE DATA IS INDICATIVE AND MAY BE REVISED WITHOUT PRIOR INTIMATION. JOHNSON CABLES WILL NOT BE LIABLE FOR ANY DAMAGES ARISING OUT OF INCORRECT APPLICATION.