Johnson Gold HRFR House Wire


Johnson Gold HRFR House Wire

APPLICABLE STANDARD : IS 694:2010
CONDUCTOR : THE CONDUCTORS DRAWN FROM 99.97 % BRIGHT ELECTROLYTIC GRADE COPPER WITH MORE THAN 100% CONDUCTIVITY ARE ANNEALED AND BUNCHED TOGETHER.
TYPE INSULATION (HRFR TYPE CPVC COMPOUND) 85°С Туре с : THE BUNCH CONDUCTORS ARE INSULATED WITH SPECIALLY FORMULATED HEAT RESISTANCE FLAME RETARDANT PVC TYPE C COMPOUD WITH A HIGH INSULATION RESISTANCE VALUE. TYPE C PVC VERY HIGH INSULATION RESISTANCE COMPARE TO PVC TYPE A INSULATION THE INSULATION PROCESS IS CARRIED OUT ON MODERN HIGH SPEED EXTRUSION LINES, WHICH ENSURES HIGH ACCURACY AND CONSISTENCY IN PERFORMANCE
OPERATING TEMPERATURE RANGE : TEMP -15°C TO MAX. +85°C
COLOUR : RED, YELLOW, BLUE, BLACK, GREEN, GRAY (AND ALSO OTHER COLOUR REQUEST ON CUSTOMER)
PACKING : COILS 90m, 100m,180m, 270m BOXES, REELS
MARKING : THE CABLES ARE PRINTED WITH GENERIC MARKING JOHNSON GOLD HRFR"
ADVANTAGE: : IMPROVED CURRENT CARRYING CAPACITY
IMPROVED HV RESISTANCE
IMPROVED LOW LEAKAGE CURRENT
HIGH INSULATION RESISTANCE
LOW ABSORPTION (WATER ABSORPTION)
SAFE FOR LONG TERM USE
VERY GOOD FLEXIBILITY
PERFORMS BETTER WHEN EXPOSED TO THE FIRE (FIRE PROPERTING)
FEATURE : ECO FRIENDLY
HIGH THERMAL STABILITY
EXTRA SAFE
20% HIGH CURRENT CARRYING CAPACITY THEN FR WIRE
HIGH INSULATION RESISTANCE
LONGER LIFE
APPLICATION : ISO 9001:2015, ISO 45001:2018, ISO 14001:2015, CE, RoHS
PRODUCT CERTIFICATION : IS 694:2010 IS 7098 P-1 , TUV RHEINLAND CERTIFICATE NO. R 60160877
SIZE DIMENSIONS AND RATING
NOMINAL CROSS SECTIONAL AREA NUMBER/ NOMINAL DIA OF WIRES (NOM.) NOMINAL THICKNESS OF INSULATION APPROX OVERALL DIA (+/-0.2 mm) MAXIMUM DC RESISTANCE OF CONDUCTOR AT 20° C MAX. CURRENT CARRYING CAPACITY
mm² Number/mm mm mm 0/km Amps
1 14/0.3 0.7 2.70 18.10 15
1.5 22/0.3 0.7 3.00 12.10 20
2.5 36/0.3 0.8 3.50 7.41 27
4 56/0.3 0.8 4.10 4.95 35
6 84/0.3 0.8 5.10 3.30 45
10 140/0.3 1.0 6.20 1.91 62
TEST DETAILS
FR
TEST SPECIFICATION SPECIFIED VALUE
CRITICAL OXYGEN INDEX ASTM-D 2863 29% MINIMUM
TEMPERATURE INDEX ASTM-D 2863 250 C MINIMUM
  • NOTE: FLEXIBLE CONDUCTOR AS PER IS 8130 THE NUMBER OF WIRES AND DIAMETER MENTIONED IN THE TABLE ARE APPROXIMATE AND NOMINAL, HOWEVER THEY SHALL MEET THE REQUIREMENTS OF CONDUCTOR RESISTANCE AS PER STANDARDS. IS 8130 THE ABOVE DATA IS INDICATIVE AND MAY BE REVISED WITHOUT PRIOR INTIMATION. JOHNSON CABLES WILL NOT BE LIABLE FOR ANY DAMAGES ARISING OUT OF INCORRECT APPLICATION.